APCs rpdu's total energy/power metric is missing

Description

Per default we only collect load from all phases

https://github.com/OpenNMS/opennms/blob/develop/opennms-base-assembly/src/main/filtered/etc/datacollection/apc.xml#L15

but the total load is missing.

rPDU2GroupTotalPower
.1.3.6.1.4.1.318.1.1.26.11.2
Getting this OID will return the total power consumption of the Rack PDU
Network Port Sharing (NPS) group devices in hundredths of kilowatts.
Queries to guest units in an NPS group are not applicable and will
return 0.

rPDU2GroupTotalEnergy
.1.3.6.1.4.1.318.1.1.26.11.3.0
Getting this OID will return the total energy consumption of the Rack PDU
Network Port Sharing (NPS) group devices in tenths of kilowatt-hours.
To reset the energy meters for each of the Rack PDU devices that contribute
to this value, see the rPDU2GroupEnergyReset OID.
To view the start time for each of the Rack PDU device energy meters that
contribute to this value, see the rPDU2DeviceStatusEnergyStartTime OID.
Queries to guest units in an NPS group are not applicable and will
return 0.

Acceptance / Success Criteria

None

Lucidchart Diagrams

Activity

Show:

Jesse White July 31, 2019 at 6:47 PM

This was actually added into 24.0.0.

Aaron Scamehorn March 14, 2019 at 7:50 PM

Hello,

I just upgraded from 22.0.2 to 23.0.3 and noticed this in the Change Log for 23.0.2. 

Curious, I looked up the issue, and saw the pull request.  I checked the commit, then compared to my local file (from the 23.0.3 rpms).

This change is NOT in the 23.0.3 RPMS.

It appears that this never made it into the release.

Ronny Trommer November 22, 2018 at 3:35 PM
Edited

Fixed